izpis_h1_title_alt

Prilagoditev ogrevalnega sistema po prenovi toplotnega ovoja stavbe
ID Mohorko, Miha (Author), ID Prek, Matjaž (Mentor) More about this mentor... This link opens in a new window

.pdfPDF - Presentation file, Download (8,03 MB)
MD5: 6A3B08F7BBE71DF564F9335A23CE9CE0

Abstract
V magistrskem delu je obravnavana prilagoditev ogrevalnega sistema po prenovi zunanjega toplotnega ovoja stavbe s poudarkom na prikazu metodologije prilagoditve centralnega ogrevalnega sistema z radiatorji. Po energijski prenovi stavbe se zmanjšajo potrebe po ogrevanju. Obstoječi radiatorji postanejo predimenzionirani, kar omogoča znižanje temperature dovodne ogrevalne vode oziroma masnega pretoka ogrevalne vode. Pri nižanju temperature dovodne ogrevalne vode smo omejeni zaradi neenakomernega zmanjšanja toplotne moči radiatorjev v posameznih prostorih. Izdelali smo program v Microsoft Excelu, da smo lahko določili obstoječemu ogrevalnemu sistemu znižano temperaturo dovodne ogrevalne vode in masni pretok ogrevalne vode. Za izbrano stavbo s projektnim temperaturnim režimom 90/70 je nova temperatura dovodne ogrevalne vode 46 °C. Izračunani masni pretok ogrevalne vode, ki ga mora zagotoviti obtočna črpalka znaša 0,5248 kg/s.

Language:Slovenian
Keywords:energijska prenova, ogrevalni sistemi, toplotna moč radiatorja, regulacijski ventili, skupna karakteristika
Work type:Master's thesis/paper
Typology:2.09 - Master's Thesis
Organization:FS - Faculty of Mechanical Engineering
Place of publishing:Ljubljana
Publisher:[M. Mohorko]
Year:2020
Number of pages:XXIV, 94 str.
PID:20.500.12556/RUL-118198 This link opens in a new window
UDC:697.4:536.7:699.86(043.2)
COBISS.SI-ID:28771587 This link opens in a new window
Publication date in RUL:26.08.2020
Views:868
Downloads:150
Metadata:XML RDF-CHPDL DC-XML DC-RDF
:
Copy citation
Share:Bookmark and Share

Secondary language

Language:English
Title:Heating system adjustment after refurbishment of building's thermal envelope
Abstract:
This master thesis examines adjustment of the heating system after refurbishment of the external thermal envelope of the building. It focuses on methodology, based on the adjustment of central-based heating system with radiators. With energy refurbishment of buildings, heating requirements are decreased. Existing radiators become oversized and heating water supply temperature or heating water mass flow can be reduced. The thermal power of radiators in individual rooms lowers unevenly which causes some limitations when decreasing the heating water supply temperature. Using a self-designed program within Microsoft Excel, we managed to determine the lowered heating water supply temperature and heating water mass flow temperature of an existing heating system. For chosen building with project temperature regime 90/70, the new heating water supply temperature is 46 °C. The calculated heating water mass flow, which the circulating pump must acquire, is 0,5248 kg/s.

Keywords:energy refurbishment, heating systems, thermal power of radiator, regulational valves, common characteristic

Similar documents

Similar works from RUL:
Similar works from other Slovenian collections:

Back