izpis_h1_title_alt

Požarno zaščitna učinkovitost vodnega transparentnega premaznega sistema za notranje lesene stenske obloge
ID Perko, Gašper (Author), ID Pavlič, Matjaž (Mentor) More about this mentor... This link opens in a new window, ID Lesar, Boštjan (Co-mentor)

.pdfPDF - Presentation file, Download (2,09 MB)
MD5: C2F69EB12C5AD374D22B43962C688EEE

Abstract
Na slovenskem trgu je na voljo kar nekaj požarno zaščitnih premazov, ki zmanjšujejo možnost vžiga in hitrost širjenja plamena po površini lesa. Njihova požarno zaščitna učinkovitost je odvisna tudi od količine nanosa in od nadaljnje površinske obdelave. V raziskavi smo proučevali vpliv različnega nanosa na požarno zaščitno učinkovitost vodnega transparentnega premaznega sistema za notranje lesene stenske obloge, ob upoštevanju doseganja želenih vizualnih lastnosti tako premazanega lesa. Prav tako smo proučili kakšen je vpliv naknadne površinske obdelave z vodnim transparentnim lakom na požarno zaščitno učinkovitost celotnega sistema. Vsem sistemom smo najprej določili osnovne lastnosti, kot so: sijaj, barva, debelina suhega filma in oprijemnost. Požarno zaščitno učinkovitost pa smo preverili z metodo malega plamena in rusko metodo. Vsi preskušeni sistemi so imeli ustrezno oprijemnost, njihov končni izgled pa je bil odvisen od sestave premaznega sistema. Najboljšo protipožarno zaščitno učinkovitost smo dosegli z 2-kratnim nanosom protipožarnega premaza, z naknadnim nanosom vodnega transparentnega laka pa se je le-ta zmanjšala, vendar za manj kot smo sicer pričakovali.

Language:Slovenian
Keywords:les, intumescenten premaz, ognjeodpornost, ruska metoda, metoda mali plamen
Work type:Bachelor thesis/paper
Typology:2.11 - Undergraduate Thesis
Organization:BF - Biotechnical Faculty
Place of publishing:Ljubljana
Publisher:[G. Perko]
Year:2022
PID:20.500.12556/RUL-140576 This link opens in a new window
UDC:630*843.1:630*829
COBISS.SI-ID:123876099 This link opens in a new window
Publication date in RUL:16.09.2022
Views:731
Downloads:71
Metadata:XML RDF-CHPDL DC-XML DC-RDF
:
Copy citation
Share:Bookmark and Share

Secondary language

Language:English
Title:Fire-retardant performance of waterborne transparent coating system for interior wooden wall coverings
Abstract:
On the Slovenian market, there is a wide range of fire protection coatings that reduce the possibility of ignition and the speed of flame spread on the wood surface. The effectiveness of fire protection also depends on the amount of such coatings applied and further surface treatments. In the study, the effect of different coating application rates on the fire protection effectiveness of a water-based transparent coating system for interior wood wall cladding was investigated, taking into account the achievement of the desired visual characteristics of the wood coated in this way. We also investigated the effect of subsequent surface finishing with water-based transparent varnish on the fire protection efficiency of the overall system. At first, the basic properties of all systems were determined, such as gloss, colour, dry film thickness and adhesion. Fire protection performance was tested using the small flame method and the Russian method. All tested systems showed sufficient adhesion, and their final appearance depended on the composition of the coating system. The best fire protection efficiency was achieved when the fire protection coating was applied twice, and it decreased when a transparent water-based varnish was subsequently applied, but to a lesser extent than expected.

Keywords:wood, intumescent coating, fire resistance, Russian method, single-flame source test