izpis_h1_title_alt

Analiza odsesovalnega sistema v izbrani mizarski delavnici : diplomsko delo - univerzitetni študij
ID Škalič, Peter (Author), ID Merhar, Miran (Mentor) More about this mentor... This link opens in a new window, ID Gornik Bučar, Dominika (Comentor), ID Šernek, Milan (Reviewer)

.pdfPDF - Presentation file, Download (6,77 MB)
MD5: 3ABE14A93E17C6D94627472A00E2970F

Abstract
Na osnovi analize nadtlačnega odsesovalnega sistema proučevane mizarske delavnice smo izdelali model odsesovalnega sistema. Meritve hitrosti pretokov in statičnih podtlakov smo izvedli z Velometrom serije 6000-P s Pitotovo cevjo. Primerjali smo trenutno, naključno postavitev loput s postavitvijo, ko so vse lopute odprte oziroma zaprte. Določili smo karakteristiko odsesovalnega sistema na podtlačnem delu cevovoda in profile hitrosti pretoka zraka za izbrana merilna mesta; ti niso vedno aksialno simetrični. Za določitev povprečne hitrosti pretoka zraka se je kot najbolj primerna pokazala eno točkovna metoda. Doseženi volumski pretoki zadostujejo za 40 % do 60 % sočasne obremenitve odsesovalnega sistema. Ventilator v cevovodu ravno tako ne razvije s strani proizvajalcev strojev predpisanega statičnega podtlaka. Predlagali smo izboljšave za trenutni odsesovalni sistem, ki je nepogrešljiv za obratovanje delavnice, kot tudi svetovali primerne konfiguracije postavitve loput za učinkovito delovanje odsesovalnega sistema. Analiza lahko predstavlja tudi osnovo za pridobitev ponudb novih bolj tehnološko dovršenih in zahtevam mizarske delavnice primernih odsesovalnih sistemov.

Language:Slovenian
Keywords:odsesovalni sistemi, filtri, cevovodi, ventilatorji, padec tlaka, volumski pretok zraka
Work type:Undergraduate thesis
Typology:2.11 - Undergraduate Thesis
Organization:BF - Biotechnical Faculty
Place of publishing:Ljubljana
Publisher:[P. Škalič]
Year:2014
Number of pages:XI, 72 f., [7] f. pril.
PID:20.500.12556/RUL-117675 This link opens in a new window
UDC:628.83:630*832
COBISS.SI-ID:2277257 This link opens in a new window
Publication date in RUL:20.07.2020
Views:1150
Downloads:191
Metadata:XML DC-XML DC-RDF
:
Copy citation
Share:Bookmark and Share

Secondary language

Language:English
Title:Analysis of the current industrial ventilation system for a carpentry shop
Abstract:
Based on the analysis of the current industrial overpressure ventilation system the model of it was created. Flow velocities and static pressure measurements were conducted with the Velometer 6000-P series for the current, completely open and closed system configuration. The characteristic curve of the system on the vacuum duct side was determined. Duct air flow velocity profiles were shown for selected measured places; these were not always axially symmetric. The duct central point velocity method was used to calculate an average flow velocity. Volume flow accounted for a simultaneous run of 40 % to 60 %. Despite the fan not providing adequate static pressure the suction ventilation system is indispensable for workshop operation. Some improvement possibilities are given as well as instructions for daily handling of the system. The investigation can provide a solid ground for making inquiries of state of the art industrial ventilation systems that match the carpentry shop demands.

Keywords:industrial ventilation systems, filters, ducts, fans, pressure loss, volumen air flow

Similar documents

Similar works from RUL:
Similar works from other Slovenian collections:

Back